- Home
- Products
- Gas Detection
- Simtronics
- Flammable Gases
- GD10P IR point Gas Detector
GD10P IR point Gas Detector
Simtronics
- General Details
- Features
- Specifications
- Documents
The Simtronics GD10P detector is the benchmark for combustible gas detection on offshore installations. It has set the standard for gas detectors in the areas of safety, stability and low maintenance. GD10P comes with 5 years warranty.
The GD10P has been designed with features that provide an effective response to the detection of gas hazards in a wide range of industrial environments from boiler plant rooms to offshore petrochemical installations.
These infrared gas detectors differ from all other models, because they utilise silicon based solid-state infrared sources. The complete optomechanical design and construction is so stable that an ultra fast speed of response can be achieved whilst providing unparalleled service life and detector stability, thus saving on maintenance and service costs.
We offer the longest combined detector and IR source warranty on the market.
For retrofit applications, a bridge interface is available allowing the detector to be connected directly to catalytic systems, using the existing cabling and control modules.
Supplied with worldwide performance and hazardous area approvals. Suitable for use in SIL 2 & SIL 3 systems.
An industry standard HART® interface is used for configuration of the optical fast response time and special fault levels as well as access to extended maintenance data.
- FPSO / FSO / MOPU
- Marine / Jack Up Rigs
- Oil & Gas Onshore Drilling Rigs
- Chemical and Petrochemical Plants
- Waste Disposal
- Gas Turbines
- General Industry
GENERAL | |
Type | Gas detector |
Product | GD10P |
Product code | GD10-P00-17DG-0X*-00 |
Manufacturer | Simtronics |
GAS DETECTOR | |
Type | Point Infrared Gas Detector |
Design principle | IR-absorption, Dual wavelength and dual path |
IR Source | Solid state (SimSource), 50Hz sampling rate, long life – 15 years warranty |
Detected gases | Common Hydrocarbons |
Calibrated range | 0 – 100%LEL Methane (CH4) |
Weather protector | Two skin baffle arrangement . Sinters, gauzes or hydrophobic filters shall not be used. |
PERFORMANCE | |
Lifetime stability | ±5% FS reading (std) |
Accuracy | ±3% FS between 0-50% reading, ±5% FS between 50-100% reading (std) |
Response time (5s – std) | T20 = 1.0 sec / T50 = 2.5 sec / T90: 6 sec |
Response time (1s – fast) | T20 = 0.3 sec / T50 = 0.7 sec / T90 = 1.4 sec (Configured via HART®) |
Calibration interval | Fixed factory calibrated. No field calibration required. |
ELECTRICAL | |
Power supply | 24V DC, range (18 – 32V DC) |
Power consumption | 140 mA typical |
Cable entry | 2x M20, one entry with Exe plug |
Junction box | Integrated Exe junction box. |
Connection | 0.3 mm2 (22 AWG) – 1.5 mm2 (16 AWG), 3 wires |
Analogue output signal | 0-20mA, max. load impedance 500Ω. |
Fault signalling | Diagnosis signalling in the 0.4 – 3.0mA range. Dirty optics / Early-dirty optics – selectable |
Maintenance interface | HART 7 |
ENVIRONMENT | |
Storage | -40°C to +70°C (-40°F to 158°F) |
Operation | -40°C to +65°C (-40°F to 149°F) |
Humidity | 100% RH (non-condensing) |
Ingress | IP66 / IP67 DIN 40050 |
RFI/EMI | Complies with EN50081-1 and EN50082-2. |
HOUSING | |
Ex Classification | EEx de IIC T6 |
Material | 316 L stainless steel |
Weight | 2.9 kg (6.4 lbs) |
Dimensions | 264L x 104W x 106H (mm)*10.4 x 4.1 x 4.2 (inches) |
APPROVALS | |
ATEX | Certificate Nemko 07ATEX1438 |
IECEx | Certificate IECEx NEM 07.0006 |
CSA | C22.2 No. 152, Certificate 1773527 |
SIL | Suitable for use in SIL3 systems |
Other | ABS, INMETRO (UL variant available) |
ACCESSORIES | |
499-811938 | Duct mount flange kit |
499-810874 | Sample flow housing |
499-813397 | Mosquito net |
499-815712 | Sunshade |