- Home
- Products
- Gas Detection
- Simtronics
- Flammable Gases
- GD10L Open Path Infrared Hydrocarbon Gas Detector
GD10L Open Path Infrared Hydrocarbon Gas Detector
Simtronics
- General Details
- Applications
- Specifications
- Documents
The GD10L provides an effective response to the detection of gas hazards in a wide range of industrial environments from boiler plant rooms to offshore petrochemical installations.
The GD10L safeguards life, environment and property through reliable gas detection over path lengths from 2 (6.5 feet) to 30m (100 feet).
The IR sources are more resistant to vibration/shock than competing technologies, hence replacement of the IR sources is not necessary during it’s long service life.
The unit combines a transmitter / receiver into a single housing and utilises a novel retro-reflector. The whole system can be commissionable by a single person.
The retro-reflector is heated to minimise condensation and icing.
5 years warranty, 15 years on IR sources
- Offshore Drilling and Production Platforms
- FPSO’s
- Refineries
- Fuel Loading Facilities
- Compressor Stations
- Chemical Plants
GENERAL | |
Type | Open Path Gas detector |
Product | Simtronics GD10L |
Product code | GD10-L0P-17GC |
Manufacturer | Simtronics |
GAS DETECTOR | |
Type | Open Path Infrared Gas Detector |
Design principle | IR-absorption, Dual wavelength and dual path, Transceiver and retro-reflector |
IR Source | Solid state, 50Hz sampling rate, long life – 15 years warranty |
Calibrated gas | Methane (CH4) |
Detected gases | Common Hydrocarbons |
Calibrated range | 0 – 5LELm |
PERFORMANCE | |
Path length | 2 – 30m |
Lifetime stability | Better than 0.2 LELm |
Repeatibility | Better than 0.1 LELm |
Response time | T50 = 2.5 sec / T90: 5 sec |
Calibration interval | Fixed factory calibrated. No field calibration required. |
ELECTRICAL | |
Power supply | 24V DC, range (18 – 32V DC) |
Power consumption | 200 mA typical |
Reflector heating | 220 or 110 VAC (specify), 120W max. |
Cable entry | M20 |
Junction box | Exe junction box. |
Connection | 0.3 mm2 (22 AWG) – 1.5 mm2 (16 AWG), 3 wires |
Analogue output signal | 0-20mA, max. load impedance 500Ω. |
Fault signalling | Diagnosis signalling in the 0 – 2.0mA range |
Maintenance interface | RS485 hand held terminal |
ENVIRONMENT | |
Storage | -40°C to +70°C (-40°F to 158°F) |
Operation | -20°C to +65°C (-4°F to 149°F) |
Humidity | 99% RH (non-condensing) |
Ingress | IP66 / IP67 DIN 40050 |
RFI/EMI | Complies with EN50081-1 and EN50082-2. |
HOUSING | |
Ex Classification | EEx de IIC T6 |
Material | 316 L stainless steel |
Weight (trcv) | 9.0 kg (14.3 lbs) |
Weight (reflector) | 14 Kg (30.8 lbs) |
APPROVALS | |
ATEX | Certificate Nemko 07ATEX1437X |
IECEX | Certificate IECEx NEM 07.0005X |
SIL | Suitable for use in SIL3 systems |
ACCESSORIES | |
419-815649 | Sunshade |
499-813183 | Gas Simulation Filter |
499-813663 | Gas Simulation Filter |
GD10-X00-TT01 | Alignment Kit |